Technical brochure
TB 1003 WG A1.70

DDF Measurements on Stator Windings – Part 2 Analysis of Results

Dielectric Dissipation Factor (DDF) measurement, also known as tangent delta (tanδ) or power factor testing, is the measurement of the dielectric losses in an Electrical Insulation System (EIS). In the field of rotating electrical machines, the method is used for assessing the condition of an EIS and the consistency in the manufacturing quality of individual stator bars/coils. Among other methods, the measurement of DDF is widely used to evaluate the quality of complete stator windings, both as an acceptance test after manufacturing and as a test to evaluate the condition of in-service stator windings due to ageing and/or contamination. 

Since updated publicly available information concerning this topic is scarce, in 2020 a new CIGRE Working Group was started to investigate DDF measurement and capacitance measurement results on complete stator windings. Such an investigation would complement the work that was already performed and published by means of TB 769 - Dielectric dissipation factor measurements on new stator bars and coils.

Convenor (NL)

M.G. KRIEG-WEZELENBURG

J.H. KRIEG (NL), H. HATANO (JP), X. CHEN (NL), T. FUJIWARA (JP), G. LEMESCH (AT), R. LUDLOW (UK), F. ÖTTL (AT), I. SIMMONDS (UK), A. SHAIKH (CA), G. VELASQUEZ (US), A. PICCOLO (IT), H. ZHU (US), A. HERRERA (DE), M. BRČIĆ (HR)

Supporting Members

A.M.H. KRIEG (NL), H. SEDDING (CA), G. SCHMIDT (DE), R. TREMBLAY (CA), J. WEIDNER (DE), D. ILIC (RS), T. TRAN (AU), D. JOVANOVIC (RS), P. WIEHE (AU), O. MONTANO (US), C. YANG (CN), R. MESSEL (US), A. VILLARRUBIA (SP), T. HILDINGER (BR), L. IMAIZUMI (BR)

Purpose, approach and response

The purpose of this Working Group is to assess and review the state-of-the-art of Dielectric Dissipation Factor (DDF) testing (at 50 Hz / 60 Hz) on form wound stator windings of rotating electrical machines, to analyse typical DDF values of new and in-service stator windings, to evaluate the effectiveness of this test and whether this method provides additional value in the process of assessing the condition of stator winding insulation. This Technical Brochure (TB) shall give the user assistance in decision making for using DDF testing as a beneficial tool in evaluation of the insulation system condition of a stator winding.

The Working Group developed three questionnaires that were internationally distributed to collect DDF measurement records of newly manufactured and in-service wound stator windings of rotating electrical machines as well as information concerning the execution of these measurements, its effectiveness, and its value for determining the insulation condition. These questionnaires were sent to Original Equipment Manufacturers (OEMs), users/owners, and third-party test companies/institutions. Each questionnaire was tailored specifically to each respondent group.

The Working Group received 71 filled questionnaires and 4466 measurement sets with DDF results on 2330 stator windings, 29 questionnaires for users/owners, 25 questionnaires for testing organizations and 17 questionnaires for manufacturers were filled in and returned. The records came from stator windings of 66 different manufacturers that were produced in 32 countries. The amount of information and measurement results received was such that it was decided to distribute the information over two Technical Brochures:

  • Part 1 – Survey answers (published in 2023 by means of TB 918)
  • Part 2 – Analysis of results

This executive summary is related to part 2 – analysis of the results.

Description of the TB

After an introduction in the first chapter, the second chapter describes the approach used to analyse the collected DDF measurement results. In this chapter the key parameters used are defined, the influence factors indicated and, most important, how to deal with all results such as single phase results versus total winding, new versus in service and the fact that from some stators more than 10 measurement results in time are available. 

The analysis focuses on three key parameters commonly used in field practice and are consistent with IEC-based interpretation: the low-voltage starting value at 0,2UN (tanδ0,2), the “tip-up” between 0,2UN and 0,6UN (Δtanδ0,6-0,2), and the maximum incremental rise between consecutive 0,2UN voltage steps (Δtanδ0,2max). These parameters are interpreted as complementary indicators: tanδ0,2 reflects baseline dielectric losses (material losses, moisture, surface leakage), while tip-up and Δtanδ0,2max highlight non-linear behaviour that may be related to surface currents caused by end potential grading or contamination effects, or partial discharge activity occurring due to voids, cracks or delamination. For understanding the concept of DDF and the physical background behind the DDF reference is made to TB 769. 

ELECTRA, is the digital magazine of CIGRE, you can obtain access as part of a CIGRE membership. Find out more about joining options here.

Already have an accountSign in

Join

A1

Power generation and electromechanical energy conversion

This Technical Brochure has been created by a Working Group from the CIGRE Power generation and electromechanical energy conversion Study Committee which is one of CIGRE's 16 domains of work.
The SC covers all aspects of electromechanical energy conversion equipment, rotating electrical machines for power generation, grid support, and energy conversion within industrial applications. This includes research, development, design, manufacture and testing of power generation and electromechanical energy conversion equipment and their associated auxiliaries, commissioning, operation, condition assessment, maintenance, life extension, refurbishment, upgrades, efficiency improvement, conversion, storage and de-commissioning.

Learn more
Top of page